XM31-918-HP - 10170104
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-918-HP
Firmware V2.06.0
Major Alarm Self test fail: output
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 117.35 V
Current 5.63 A
Power 598 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 9,260 Wh
Output
Voltage 60.50 V
Power 484 W
Apparent Power 531.79 VA
Frequency 59.99 Hz
Percent Load 48.80 %
Output Setting 60 V
Output Regulation Coarse override
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Active Drop Alarm OK
Active Drop Threshold 50 W
Current 8.79 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Enable
Total Standby Events 16
Time Since Last Standby Event 0d 0h:00m
Time in Last Standby Event 0d 0h:00m
Total Time in Standby 139 min
Standby Events Since Reset 1
Time in Standby Since Reset 0 min
Time Since Reset 100 day(s)
Total Run Time 100 day(s)
Transformer Run Time 100 day(s)
Total Downtime 0d 0h:00m
Oil Cap Lifespan Consumed 1.7 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 23 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 
Copyright © 2017-2023 EnerSys. All Rights Reserved.